Insulation Resistance Test

What is Required Insulation Resistance Test?

The Insulation Resistance Test (commonly abbreviated as IR Test) is a critical electrical test used to evaluate the integrity of insulation materials in electrical equipment. The “required” Insulation Resistance Test refers to the mandatory or standard-compliant testing of insulation resistance as per national or international regulations (like IEC, IEEE, IS, or NFPA).


🧪 Definition:

A Required Insulation Resistance Test is the standardized measurement of electrical resistance (in megaohms, MΩ) between conductors and earth (or between conductors) using a DC voltage to ensure the insulation is adequate to prevent leakage current, short circuits, or electric shocks.


⚙️ Key Parameters:

ParameterDescription
Test VoltageTypically 250V, 500V, or 1000V DC (based on equipment)
Resistance ThresholdMinimum values (e.g., 1 MΩ or higher depending on voltage)
Test EquipmentInsulation Resistance Tester or Megger

🧰 Why is it Required?

  1. Safety – Prevents electrical shock hazards.
  2. Reliability – Ensures continued performance of equipment.
  3. Compliance – Required by IEC 60364, IS 732, NFPA 70, etc.
  4. Preventive Maintenance – Detects aging, moisture, or damage in insulation.
  5. Commissioning Test – Part of pre-operational testing of new installations.

🏗️ Applications:

  • Power cables & wiring
  • Transformers
  • Motors and generators
  • Circuit breakers
  • Electrical panels
  • HVAC systems

📋 Typical Test Procedure:

  1. Disconnect equipment from power.
  2. Discharge all stored energy.
  3. Connect IR tester across:
    • Phase to Earth
    • Phase to Neutral
    • Phase to Phase
  4. Apply test voltage (e.g., 500V).
  5. Record resistance. Ensure values meet or exceed standard thresholds.
  6. Discharge equipment again before reconnection.

📌 Minimum Acceptable Values (as per IEC/IS):

Equipment Voltage RatingMinimum Insulation Resistance
≤ 250V0.5 MΩ
250V – 500V1.0 MΩ
> 500V1.0 MΩ or 1 MΩ/kV

Who is Required Insulation Resistance Test?

Insulation Resistance Test

The Required Insulation Resistance Test must be conducted by qualified personnel across multiple sectors and industries to comply with safety, legal, and operational standards. Here’s a breakdown of who needs to perform or mandate this test:


👷‍♂️ 1. Electrical Engineers & Technicians

  • Responsibility: Performing insulation resistance tests using IR testers or meggers.
  • Context: During installation, maintenance, fault finding, and shutdown procedures.

🏭 2. Industrial and Commercial Establishments

  • Who Requires It: Maintenance departments of:
    • Manufacturing plants
    • Data centers
    • Oil & gas refineries
    • Power plants
    • Chemical factories
  • Why: To ensure electrical equipment operates safely and to avoid unplanned downtime.

🏢 3. Building Owners, Facility Managers, and Contractors

  • Where: In residential, commercial, and institutional buildings.
  • Why: As part of periodic inspection, commissioning, or handover of buildings (per IS 732, IEC 60364 or NFPA 70).

🧰 4. Testing, Inspection, and Certification Bodies

  • Examples: NABL-accredited labs, third-party inspection agencies.
  • Why: To issue test certificates for compliance, audits, and quality checks.

⚡ 5. Utility Companies and Energy Providers

  • Requirement: For grid-connected equipment like:
    • Transmission cables
    • Distribution boards
    • Switchgear installations
  • When: During preventive maintenance or before energization.

📜 6. Regulatory and Statutory Authorities

  • Examples:
    • Indian Electricity Rules (CEA)
    • OSHA (USA)
    • IEC/IS/NFPA standards
  • Why: To enforce compliance with national and international safety codes.

🎓 7. Training Institutions and Technical Education Bodies

  • Purpose: To teach students and trainees the practice of insulation resistance testing as part of electrical safety modules.

✅ Summary Table:

WhoWhy Required
Electrical Engineers/TechniciansTesting & maintenance of insulation
Industrial/Commercial UnitsOperational safety and asset protection
Facility Managers/ContractorsCompliance with installation codes
Certification & Audit BodiesIssue reports and ensure code compliance
Utility CompaniesGrid safety and commissioning of electrical systems
Regulatory AuthoritiesEnforcing legal compliance
Training InstitutesSkill development in electrical safety

When is Required Insulation Resistance Test?

Courtesy: Fluke Corporation

The Insulation Resistance Test (IR Test) is required at specific stages throughout the lifecycle of electrical systems and equipment. It is mandated by national and international standards to ensure safety, functionality, and compliance.


📅 Key Times When Insulation Resistance Test is Required:


1. Before Energizing New Installations (Pre-Commissioning)

  • Why: To verify insulation integrity before powering up.
  • Standards: IS 732, IEC 60364, NFPA 70.
  • Applies To: Cables, panels, motors, transformers, generators.

2. During Periodic Maintenance (Routine Testing)

  • Frequency: Typically every 6 to 12 months, or as per risk assessment.
  • Why: To monitor insulation degradation over time.
  • Industries: Industrial plants, hospitals, IT data centers, commercial buildings.

3. After Repairs, Modifications, or Upgrades

  • Why: To ensure insulation was not compromised during service work.
  • Applies To: Any repaired motor, cable, control panel, or substation component.

4. After Prolonged Shutdown or Storage

  • Why: Moisture absorption or insulation aging can occur during disuse.
  • When: Before restarting idle machinery or installations.

5. During Trouble-Shooting or Fault-Finding

  • Why: To identify short circuits, leakage paths, or damaged insulation.
  • Examples: Tripped breakers, unexplained voltage drops, or system faults.

6. During Audits, Inspections, or Compliance Checks

  • Who Requires It: Certification bodies, safety auditors, government inspectors.
  • When: During ISO, CE, BIS, or statutory audits and inspections.

7. During Manufacturing or Quality Control

  • Where: In factories producing motors, cables, transformers, and panels.
  • Why: To verify insulation strength before shipping to customers.

📌 Summary Table:

WhenPurpose
Pre-commissioningEnsure initial safety before energizing
Scheduled maintenanceMonitor insulation health
Post-repair or upgradeRe-check system integrity
After long shutdownsConfirm no degradation due to environment
Fault analysisLocate insulation-related failures
During audits/inspectionsCompliance with codes and standards
In manufacturing (type/routine tests)Assure product quality

Where is Required Insulation Resistance Test?

The Insulation Resistance Test is required across diverse locations wherever electrical systems or equipment are installed, operated, manufactured, or maintained. It is a universal safety test applicable in industrial, commercial, residential, and infrastructure environments.


🏭 1. Industrial Locations

  • Examples:
    • Manufacturing plants
    • Chemical factories
    • Power plants (thermal, hydro, nuclear)
    • Oil & gas refineries
  • What’s Tested: Motors, control panels, switchgear, cables, transformers.

🏢 2. Commercial and Office Buildings

  • Examples:
    • Malls, IT parks, hospitals, hotels, data centers
  • What’s Tested: Distribution boards, wiring systems, HVAC systems, UPS units.
  • Why: Required during installation, AMC, and audits.

🏠 3. Residential Complexes and Housing Societies

  • What’s Tested: Final sub-circuits, wiring, earth leakage paths.
  • Why: For compliance with IS 732 and building codes.

4. Electrical Substations and Power Distribution Areas

  • What’s Tested: Busbars, transformers, circuit breakers, relays.
  • Standards Followed: IEC 60060, IS 2026, IS 3420, etc.

🚧 5. Construction and Commissioning Sites

  • What’s Tested: Temporary site wiring, lighting circuits, new equipment before handover.
  • Why: To ensure safety of on-site workers and meet safety regulations.

🏫 6. Educational and Training Institutions

  • Use: As part of practical training in ITIs, engineering colleges, and polytechnics.
  • Test Areas: Lab setups, demo panels, training equipment.

🏢 7. Government and Statutory Inspections

  • Who Conducts: Electrical inspectors, fire safety officers, energy auditors.
  • Where: Public infrastructure, metro rail systems, airports, smart city zones.

🛠️ 8. Testing & Calibration Laboratories

  • What’s Tested: Products undergoing type testing, routine testing, or batch acceptance.
  • Where: NABL/ILAC-accredited labs or in-house QA labs of manufacturers.

🌐 9. Remote and Hazardous Environments

  • Examples: Offshore rigs, underground mines, defense installations.
  • Why: To prevent insulation failure in high-risk or inaccessible zones.

📌 Summary Table:

LocationEquipment/Systems Tested
Industrial plantsMotors, panels, cables, MCCs
Commercial buildingsDBs, HVAC, UPS, server racks
Residential apartmentsInternal wiring, ELCBs, final circuits
Power stations & substationsTransformers, CT/PT units, breakers
Construction sitesTemporary wiring, construction tools
Schools & training centersElectrical lab setups
Testing & certification labsElectrical products under evaluation
Government/public infrastructureRailways, airports, hospitals, smart grid setups
Hazard-prone areasExplosion-proof enclosures, ATEX-rated equipment

How is Required Insulation Resistance Test?

Insulation Resistance Test 2

The Required Insulation Resistance Test is carried out using a megohmmeter (IR tester) to apply high DC voltage and measure the resistance of electrical insulation between conductors and/or between conductor and earth. This test evaluates whether the insulation is effective enough to prevent current leakage, electrical shock, or equipment failure.


🧪 Step-by-Step Procedure for Insulation Resistance Testing:


✅ 1. Preparation

  • Power Off: Completely de-energize the equipment.
  • Discharge: Discharge capacitors or any stored charge using grounding sticks.
  • Isolation: Disconnect the equipment under test from other systems (to avoid parallel paths or false readings).
  • Label and Secure Area: Use safety barriers and signage to prevent accidental contact during testing.

✅ 2. Select Test Points

  • Phase to Earth (L–E)
  • Phase to Neutral (L–N)
  • Phase to Phase (L1–L2, L2–L3, etc.)

✅ 3. Connect IR Tester

  • Use proper-rated test leads from the IR tester (megger).
  • Connect one lead to each test point (e.g., L–E).

✅ 4. Set Test Voltage

Choose voltage level depending on system:

Equipment VoltageTest Voltage (DC)
Up to 250 V500 V
250–500 V500 V – 1000 V
>1000 V1000 V – 5000 V

⚠️ Use manufacturer guidelines or IEC/IS standards to determine exact test voltage.


✅ 5. Apply Voltage and Measure

  • Press the test button on the IR tester.
  • Wait for 10–60 seconds to allow stable reading.
  • Note the resistance value in MΩ (megaohms).

✅ 6. Interpret Results

  • Compare against standard thresholds (e.g., ≥1 MΩ for most low-voltage circuits).
  • Very high values (∞ or >1000 MΩ) indicate good insulation.
  • Low or zero values indicate insulation breakdown or moisture.

✅ 7. Post-Test Procedures

  • Safely discharge tested equipment again (very important).
  • Reconnect circuits or cables that were isolated.
  • Document test results for compliance or record-keeping.

🔧 Tools and Equipment Used:

  • Megger/IR Tester
  • Safety gloves and shoes
  • Insulation test leads
  • Lockout/tagout (LOTO) devices
  • Grounding rod (for discharge)

📋 Sample Insulation Resistance Values (IEC/IS Recommendations):

System/EquipmentMinimum IR Value
Residential wiring≥1 MΩ
Motors (LV < 1kV)≥1 MΩ per kV + aging factor
Transformers≥100 MΩ (depends on class)
Control panels≥1 MΩ
Cables (new)≥5 MΩ/km

🧠 Best Practices:

  • Perform tests in dry conditions.
  • Use calibrated instruments.
  • Avoid testing near flammable gases or wet environments.
  • Repeat tests periodically to monitor insulation degradation.

Case Study on Insulation Resistance Test?

Title: Preventive Failure Detection in Industrial Motor Using Insulation Resistance Test


🔍 Background:

A large manufacturing plant operating 24/7 for automotive component production in Pune, India, relies heavily on 3-phase induction motors. During a routine maintenance inspection, one of the 75 kW motors responsible for conveyor belt movement showed unusual heat rise and occasional tripping.

The maintenance team decided to perform a Required Insulation Resistance Test as part of the diagnostic process.


🎯 Objective:

To detect possible insulation degradation and prevent motor failure or downtime using standardized IR testing procedures.


🧪 Methodology:

Equipment Under Test:

  • 3-phase squirrel cage induction motor (75 kW, 415V, star connected, 50 Hz)
  • Age: 5.5 years
  • Operating environment: High humidity (>75%), dusty

Test Instrument Used:

  • Digital IR Tester (Megger Make, 1000V range)

Test Points:

  • Phase to Earth (R–E, Y–E, B–E)
  • Phase to Phase (R–Y, Y–B, B–R)

Test Voltage Applied:

  • 1000V DC (as per IS/IEC 60034-1 for >1kV rated motors)

📈 Results:

Test PointMeasured ResistanceStandard LimitStatus
R–E0.3 MΩ≥1 MΩ❌ Failed
Y–E0.7 MΩ≥1 MΩ❌ Failed
B–E1.1 MΩ≥1 MΩ✅ Passed
R–Y2.5 MΩ≥1 MΩ✅ Passed
Y–B2.1 MΩ≥1 MΩ✅ Passed
B–R2.3 MΩ≥1 MΩ✅ Passed

⚠️ Findings:

  • The R–E and Y–E insulation resistance values were below acceptable limits, indicating moisture ingress and beginning phase of insulation failure.
  • The motor windings were exposed to high humidity, dust, and lacked regular thermal drying procedures.

🛠️ Corrective Actions Taken:

  1. Motor disconnected and removed from service.
  2. Infrared drying of windings carried out.
  3. Insulation revarnishing done with Class F varnish.
  4. Motor retested after drying:
Test PointRetested Resistance
R–E10.2 MΩ
Y–E11.5 MΩ
B–E12.1 MΩ

✅ All readings were within safe limits.


🧾 Conclusion:

  • IR Test helped prevent unplanned downtime and potential equipment failure worth ₹8–10 lakhs.
  • Established the importance of scheduled insulation resistance testing every 3 months, especially in humid environments.
  • The plant adopted a policy of predictive maintenance using IR and thermography to monitor insulation health of critical assets.

📌 Key Takeaways:

  • Low IR values are early indicators of insulation degradation.
  • Regular IR testing can save costs, extend equipment life, and ensure worker safety.
  • Combining IR testing with thermal imaging and polarization index (PI) tests enhances reliability.

White paper on Insulation Resistance Test?

Courtesy: Megger

Title: Ensuring Electrical Safety and Reliability through Insulation Resistance Testing
Author: Six Sigma Labs – Technical Division
Date: June 2025


🔍 Executive Summary

The Insulation Resistance Test (IR Test) is a foundational technique for assessing the health of electrical insulation in equipment and systems. With increasing industrial complexity and safety regulations, IR testing has become a mandatory procedure for preventive maintenance, commissioning, and quality assurance. This white paper provides a comprehensive understanding of the principles, methods, standards, applications, and benefits of insulation resistance testing.


1️⃣ Introduction

In electrical systems, insulation failure is one of the leading causes of short circuits, equipment damage, and fire hazards. The insulation resistance test is used to evaluate the ability of electrical insulation to resist current flow, thereby preventing leakage, energy loss, and safety incidents.


2️⃣ Fundamentals of Insulation Resistance

  • Definition: The resistance offered by insulation to the flow of leakage current.
  • Measured In: Megaohms (MΩ)
  • Test Method: Application of a DC voltage across the insulation and measuring resulting current.
  • Typical Test Voltages: 250V, 500V, 1000V, 2500V, 5000V DC

3️⃣ Testing Procedure

StepDescription
PreparationDe-energize, isolate, and discharge equipment
Selection of Test PointsPhase–Earth, Phase–Neutral, Phase–Phase
Application of Test VoltageUse IR tester to apply standardized DC voltage
Measurement and ObservationRead resistance values after 30–60 seconds
DocumentationRecord results for compliance and traceability

4️⃣ Standards and Compliance

StandardDescription
IS 732Code of practice for electrical wiring installations
IEC 60364Low-voltage electrical installations
IEEE 43Testing insulation resistance of rotating machinery
NFPA 70 (NEC)National Electrical Code (USA)

5️⃣ Minimum Acceptable Values

Equipment/InstallationMinimum Insulation Resistance
Low-voltage residential≥ 1 MΩ
Motors (per kV)≥ 1 MΩ per kV + aging factor
Transformers≥ 100 MΩ (HV side)
Control panels and wiring≥ 1–2 MΩ

6️⃣ Industrial Applications

  • Power Plants: Transformers, switchgear, control rooms
  • Manufacturing Units: Motors, PLC panels, conveyor systems
  • Commercial Buildings: Wiring, UPS systems, HVAC controls
  • Railways and Airports: Signal systems, substations
  • Oil & Gas: Hazardous area equipment, flameproof circuits

7️⃣ Benefits of Insulation Resistance Testing

  • ✔️ Early Detection of insulation deterioration
  • ✔️ Prevention of Electrical Failures
  • ✔️ Ensures Personnel Safety
  • ✔️ Compliance with Legal Standards
  • ✔️ Supports Predictive Maintenance Programs

8️⃣ Case Study Snapshot

Client: Automotive OEM Plant
Issue: Motor tripping due to insulation breakdown
IR Test Findings: R–E: 0.3 MΩ (Fail)
Solution: Drying, varnishing, and retesting
Outcome: Prevented failure and saved ₹10 lakh in downtime


9️⃣ Challenges & Recommendations

ChallengeRecommendation
Fluctuating ResultsStandardize environmental conditions
Equipment DowntimeUse off-peak hours for IR testing
Inadequate RecordkeepingImplement digital maintenance logs
Misapplication of Test VoltageTrain technicians per IS/IEC guidelines

🔟 Conclusion

Insulation resistance testing is not just a technical requirement—it’s a strategic tool for ensuring electrical safety, operational efficiency, and regulatory compliance. Regular testing, when integrated into preventive maintenance schedules, significantly enhances equipment reliability and plant productivity.


📎 Appendices

  • ✅ IR Test Report Template
  • ✅ IR Tester Calibration Log
  • ✅ Polarization Index (PI) Testing Overview
  • ✅ Comparison with Dielectric Strength Test

Industrial Application of Insulation Resistance Test?

The Insulation Resistance Test is widely used across industries as a critical diagnostic and safety tool. It ensures electrical insulation integrity, reduces the risk of failures, and complies with regulatory standards. Below is a detailed look at its applications across key industries.


⚙️ 1. Manufacturing Industry

  • Applications:
    • Motors, drives, and control panels
    • Conveyor systems and automation panels
  • Purpose:
    • Prevent production downtime due to electrical faults
    • Schedule predictive maintenance
  • Standards Used: IS 732, IEC 60034

⚡ 2. Power Generation and Distribution

  • Applications:
    • Transformers, circuit breakers, switchgear, CT/PT units
    • High-voltage cables and busbars
  • Purpose:
    • Ensure insulation health before energizing substations
    • Meet safety and load flow requirements
  • Standards: IS 2026, IEEE 43, IEC 61869

🛢️ 3. Oil and Gas Industry

  • Applications:
    • Flameproof motors, ATEX-rated equipment
    • Cables in hazardous zones (Zone 1/Zone 2)
  • Purpose:
    • Prevent arcing or sparking in explosive atmospheres
    • Maintain continuous operation of critical equipment
  • Special Notes: Must comply with ATEX and IECEx requirements

🏗️ 4. Construction and Infrastructure Projects

  • Applications:
    • Temporary and permanent electrical installations
    • Lighting systems, elevators, pumps
  • Purpose:
    • Validate safety before handover
    • Obtain occupancy and compliance certification (IS 732)
  • Who Uses: Contractors, electrical inspectors, developers

🏢 5. Commercial Buildings and Data Centers

  • Applications:
    • UPS systems, emergency lighting, HVAC
    • Server room power cabling
  • Purpose:
    • Prevent unexpected power failures
    • Maintain high uptime and fire safety
  • Testing Frequency: Semi-annually or during preventive maintenance shutdowns

🚆 6. Railways and Metro Systems

  • Applications:
    • Trackside power systems, signal circuits, substation panels
  • Purpose:
    • Ensure fault-free operation of signalling and control systems
  • Relevant Standards: RDSO, IS 3072, IEC 61373

✈️ 7. Aerospace and Airports

  • Applications:
    • Runway lighting, terminal distribution panels, radar installations
  • Purpose:
    • Ensure insulation quality in critical systems exposed to weather
    • Comply with DGCA, FAA, and ICAO guidelines

🏥 8. Hospitals and Healthcare Facilities

  • Applications:
    • Operation theatres, medical equipment circuits, emergency systems
  • Purpose:
    • Avoid insulation faults that could endanger patient safety
  • Regulations: NFPA 99, IEC 60601-1

🏘️ 9. Residential Societies & Smart Homes

  • Applications:
    • Wiring networks, inverters, solar connections
  • Purpose:
    • Fire prevention and compliance with building codes (IS 732)
  • When Used: At handover or during electrical inspections

🔧 10. OEMs and Product Manufacturers

  • Applications:
    • Final testing of electrical products: motors, pumps, panels, heaters
  • Purpose:
    • Quality assurance (routine & type testing)
    • Meet certification requirements (CE, BIS, UL)

📌 Summary Table:

IndustryKey EquipmentPurpose
Power & UtilitiesTransformers, cables, switchgearGrid reliability and safety
ManufacturingMotors, panels, PLCsDowntime prevention, asset longevity
Oil & GasFlameproof equipment, zone circuitsExplosion prevention
Infrastructure/ConstructionAll fixed installationsCompliance before commissioning
Commercial & Data CentersHVAC, UPS, wiringSystem integrity and fire protection
Railways & AirportsControl systems, lightingSafe transport operations
HealthcareLife-saving electrical systemsPatient and personnel safety
ResidentialDomestic wiringSafety compliance and fire prevention

References

  1. ^ “A guide to insulation resistance testing” (PDF). Biddle Megger. Archived from the original (PDF) on 2009-02-06.
  2. Jump up to:a b “Electrical Safety Tests”EBME.co.uk. Retrieved 18 February 2016.
  3. ^ Wilson, Richard (15 November 2013). “Know your MOPPS from your MOOPS in medical power supply design”Electronics Weekly. Retrieved 18 February 2016.
  4. ^ Wilson, Richard (15 November 2013). “Know your MOPPS from your MOOPS in medical power supply design”Electronics Weekly. Retrieved 18 February 2016.
  5. ^ “AAMI Standards and Recommended Practices” (PDF). aami.org. American National Standards Institute, Inc. Archived from the original (PDF) on 2015-09-21.
  6. ^ “CAN/CSA-C22.2 NO. 60601-1:08 (R2013)”scc.ca. Standards Council of Canada. 11 September 2023.
  7. ^ Bayliss, Ann-Marie. “Understanding the 3rd edition medical safety standard and using DC-DC converters to provide isolation” (PDF). go.murata.com. Murata.
  8. Jump up to:a b c “Medical Approvals for Power Supplies” (PDF). epsma.org. EPSMA.[dead link]
  9. ^ “MOPP and MOOP in IEC 60601-1 3rd” (PDF). Mouser.com.
  10.  “Understanding Insulation Resistance Testing”Electrical Construction & Maintenance (EC&M) Magazine. 1996-01-01. Retrieved 2019-08-14.
  11. ^ “Electrical Isolation | Transformers | Electronics Textbook”www.allaboutcircuits.com. Retrieved 2019-08-14.
  12. ^ Electrical Isolation Verification (DC) Practice No. PT-TE1417, Preferred Reliability Practices, NASA
  13.  “Low Voltage Directive (LVD) – European Commission”single-market-economy.ec.europa.eu. Retrieved 2024-04-07.
  14. ^ “Catalogue Item”www.standards.org.au. Retrieved 2024-04-07.
  15. ^ “PAT (Portable appliance testing) – HSE’s answers to popular questions”www.hse.gov.uk. Retrieved 2023-10-04.
  16. ^ Health and Safety Executive, Electrical safety and you
  17. ^ Maintaining portable electric equipment in low-risk environment
  18. ^ “Electrical Landlord Certificates: What you need to know | Blog Post | Premier Electrical Company”electricians-portsmouth.co.uk.
  19. ^ “Faults and electrical safety”. Archived from the original on 2016-01-12. Retrieved 2015-12-29.
  20. ^ Standard: AS/NZS 3760:2003 In-service inspection and testing of electrical equipment Sec 2.3.3.1
  21. ^ Standard: AS/NZS 3760:2003 In-service inspection and testing of electrical equipment Sec 2.3.3.2(b). General
  22. ^ Standard: AS/NZS 3760:2003 In-service inspection and testing of electrical equipment Sec 2. 3.3.2(a)
  23. ^ BS 7671 wiring rules
  24. ^ Best Practices in Testing & Tagging of Electrical Equipment to AS/NZS 3760:2003. (Zahra & Virieux 2007) 5.8.1
  25. Jump up to:a b “How do I PAT test a microwave? | PAT FAQ’s”.
  26. ^ “Electrical Equipment Maintenance and Testing (2377)”. City&Guilds. 25 July 2022. Retrieved 18 September 2023.
  27. ^ The Institution of Engineering and Technology (21 October 2020). Code of Practice for In-service Inspection and Testing of Electrical Equipment – 5th Edition. The Institution of Engineering and Technology. ISBN 978-1785619663.
  28. ^ [1] What Is AS/NZS 3760?
  29.  “NEMA Insulation Classes”www.engineeringtoolbox.com.
  30. ^ E. Alfredo Campo (ed.), Selection of polymeric materials: how to select design properties from different standards William Andrew, 2007 ISBN 0-8155-1551-0 page 170
  31. Jump up to:a b c International Electrotechnical Commission Standard 60085 Electrical Insulation- Thermal Evaluation and Designation, 3rd edition, 2004 ,page 11 table 1
  32. ^ IEC 60085:2007 Table 1
  33. ^ NEMA standard MG-1 Motors and Generators
  34. ^ M. A. Laughton, D. F. Warne (ed), Electrical engineer’s reference book, 16th edition Newnes, 2003 ISBN 0-7506-4637-3, page 7-3
  35. ^ Donald G. Fink and Wayne H. Beaty (ed), Standard Handbook for Electrical Engineers, Eleventh Edition, Mc Graw Hill, 1978, ISBN 0-07-020974-X, page 7-12
  36. ^ “Understanding IEC Appliance Insulation Classes: I, II and III”Fidus Power. 6 July 2018. Archived from the original on 17 February 2020. Retrieved 16 October 2018.

Table of Contents

Leave a Comment

Your email address will not be published. Required fields are marked *

Follow Us

swachh_bharat
made_in_india
beti_bachao
75th independence day
swachh_bharat
made_in_india
beti_bachao
75th independence day

2025. Copyright sixsigma-tqm.in